DistriView V9.5 Bug Alert

We recently discovered and fixed the following bugs in DistriView version 9.5:



1) The DVT file system base MVA could be altered inadvertently by these steps: Execute the Add Transformer Damage Curve command and select the Manual option.  Then press the "Get Data from a Transformer" button, type in or select a value in MVA rating combo box and press the OK button.



2) The generator short circuit current shown in the one-line diagram did not agree with the current flowing into the adjacent branch.  This problem happens only  if you are using the "Start from a full, non-linear voltage-drop solution" prefault voltage option, and the generator is set to generate a fixed amount of kW and kVAR.



3) The Phasor Probe was not showing the phase current from a synchronous generator.



4)  DistriView did not shift the transformer damage curve correctly when the linked relay did not operate and automatic horizontal shift curve option is in effect.



We plan to release a DistriView version 9.6 with all the bug fixes within the next two weeks.