Issue in Breaker Rating Module calculation

We had discovered that due to a software bug in the Breaker Rating Module the program did not always carry out all required fault simulations in checking rating of some breakers with protected equipment lists that include additional outages. As the results the checking report can show inaccurate worst case rating duty percent for some of these breakers.


This error had been fixed in OneLiner version 14.5 with build number 45068 and higher (Program version and build number are displayed in OneLiner Help | About dialog box).


Users should contact ASPEN support to request program update with the bug fix.

Recent Posts

See All
OneLiner iterative solution

We discovered a software bug in the simulation results reporting logic in OneLiner V15.7 and earlier. When the iterative solution of some...

 
 
 