Issue in OneLiner simulation of SEL distance relay directional element

We found that the program did not correctly calculate the directional element of distance relay types: SEL311P__, SEL311G__, SEL421P__, SEL421G__, SEL411P__  SEL411G__ when the value of the E32 setting is AUTO.


This error had been fixed in OneLiner version 14.7 with build number 58027 and higher (Program version and build number are displayed in OneLiner Help | About dialog box).


Users should contact ASPEN support to request program update with the bug fix.

Recent Posts

See All
OneLiner iterative solution

We discovered a software bug in the simulation results reporting logic in OneLiner V15.7 and earlier. When the iterative solution of some...

 
 
 