top of page

POST

Issue in OneLiner V14 ANSI x/r results

Updated: Jan 9, 2024

We discovered that OneLiner V14 produced incorrect ANSI x/r results in some networks when fault simulation options of "Iterative short circuit solution" of MOV protected series capacitor and/or "Enforce current limit" of current limited generators are enabled. These errors could potentially affect the Breaker Rating Module results as well.



This programming error had been fixed in OneLiner V14.3 with build number 30575 and higher (Program build number is display in OneLiner Help | About dialog box). Users should contact ASPEN support to request program update with this bug fix.

Recent Posts

See All
OneLiner iterative solution

We discovered a software bug in the simulation results reporting logic in OneLiner V15.7 and earlier. When the iterative solution of some...

 
 
 

Comments


©1986-2025 Advanced Systems for Power Engineering, Inc. All Rights Reserved.

bottom of page